Many Electromagnetic time reversal (EMTR)-based fault location methods were proposed in the latest decade. In this paper, we briefly review the EMTR-based fault location method using direct convolution (EMTR-conv) and generalize it to multi-phase transmission lines. Moreover, noting that the parameters of real transmission lines are frequency-dependent, while constant-parameters were often used during the reverse process of EMTR-based methods in the previous studies, we investigate the influence of this simplification to the fault location performance by considering frequency-dependent parameters and lossy ground in the forward process which shows the location error increases as the distance between the observation point and the fault position increases, especially when the ground resistivity is high. Therefore, we propose a correction method to reduce the location error by using double observation points. Numerical experiments are carried out in a 3-phase 300-km transmission line considering different ground resistivities, fault types and fault conditions, which shows the method gives good location errors and works efficiently via direct convolution of the signals collected from the fault and the pre-stored calculated transient signals.
翻译:近十年来,提出了许多基于电磁时间逆转(EMTR)的故障定位方法。在本文中,我们简要地审查了基于EMTR的故障定位方法,使用直接变速(EMTR-conv),并将其概括为多相传输线。此外,我们注意到,实际传输线的参数取决于频率,而在以往研究中,在基于EMTR的方法的逆向过程中,经常使用常数参数,而这种简化对故障定位性能的影响是,我们考虑到前方进程中的频率依赖参数和损失地,表明由于观测点与断断点之间的距离增加,定位错误增加,特别是在地面阻力高的情况下。因此,我们提出一种纠正方法,通过使用双向观测点减少地点错误。考虑到不同的地面抵抗力、断层类型和断层条件,在3-300公里传输线中进行数值实验,这表明该方法通过从断层和预算的中信号的直接连动,使定位错误和工作效率很高。